MEAN WELL LAD-120 Series 120W Security Power Supply with Battery Charger & UPS Function

The MEAN WELL LAD-120 Series is a compact 120W AC/DC security and fire alarm power supply with built-in battery charger and UPS backup function, designed for systems that require regulated DC power, battery charging and continued operation during AC mains interruption.

The series accepts a universal 90–264VAC input or 127–370VDC input and is available in four output versions: LAD-120A with 13.8V output and up to 7.7A rated current, LAD-120B with 27.6V output and up to 3.4A, LAD-120C with 41.5V output and up to 1.9A, and LAD-120D with 55.2V output and up to 1.21A. Each model provides a dedicated 1A battery charging output and supports lead-acid and lithium-ion batteries.

During normal AC operation, the LAD-120 supplies power to the connected load while charging the backup battery. If the AC mains supply becomes abnormal, the built-in UPS function switches the system to battery backup operation. The series also provides TTL status signals for AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge status, together with a forced UPS mode for battery maintenance and system testing.

With a low-profile 159 × 97 × 30 mm design, built-in AC and battery circuit ON/OFF switches, and protection against short circuit, overload, overvoltage, overtemperature, battery low voltage and battery reverse polarity, the LAD-120 Series is suitable for security systems, fire emergency and evacuation systems, public safety battery backup, DC UPS systems, central monitoring systems and industrial automation.

MEAN WELL LAD-120 Series 120W power supply with battery charger and UPS function
MEAN WELL LAD-120 Series 120W security and fire alarm power supply with built-in battery charger and UPS backup function.

Key Highlights of LAD-120 Series

  • 120W AC/DC security and fire alarm power supply with built-in battery charger and UPS backup function
  • Universal 90–264VAC input with 127–370VDC input capability and up to 88% typical efficiency
  • Available as LAD-120A, LAD-120B, LAD-120C and LAD-120D with 13.8V, 27.6V, 41.5V and 55.2V outputs
  • Supports normal load powering, battery charging and automatic battery backup operation when AC mains becomes abnormal
  • TTL status signals provide AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge monitoring
  • Forced UPS mode supports battery maintenance and system testing through the CN2 control interface
  • Built-in short circuit, overload, overvoltage, overtemperature, battery low-voltage and reverse-polarity protection
  • Compact 159 × 97 × 30 mm low-profile design for security, fire emergency, DC UPS, central monitoring and industrial automation systems

Overview of MEAN WELL LAD-120 Series

The MEAN WELL LAD-120 Series combines regulated DC output, dedicated battery charging, UPS backup control and system status monitoring in a compact 120W AC/DC power supply. It is designed for security, fire alarm and backup power applications that require normal DC operation together with automatic battery-supported operation when AC mains power becomes abnormal.

During normal AC operation, the LAD-120 supplies power to the connected load while charging the external battery. If the AC input becomes abnormal, the built-in UPS function switches the power source to battery backup, allowing connected equipment to continue operating during mains interruption. The series also supports a forced UPS mode for battery maintenance and system testing.

The series includes four models. LAD-120A provides a 13.8V main output rated at 7.7A, LAD-120B provides 27.6V at 3.4A, LAD-120C provides 41.5V at 1.9A, and LAD-120D provides 55.2V at 1.21A. Each model also provides a dedicated 1A battery charging output, and the series is suitable for use with lead-acid and lithium-ion batteries.

For system monitoring, the LAD-120 Series provides TTL status signals for AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge status. Built-in protection functions include short circuit, overload, overvoltage, overtemperature, battery low-voltage protection and battery reverse-polarity protection. With a compact 159 × 97 × 30 mm low-profile design and built-in AC and battery circuit ON/OFF switches, the LAD-120 Series is suitable for security systems, fire emergency and evacuation systems, public safety battery backup, DC UPS systems, central monitoring systems and industrial automation.

Features

  • 120W AC/DC security and fire alarm power supply with dedicated main output and 1A battery charging output
  • Universal 90–264VAC input with 127–370VDC input capability and up to 88% typical efficiency
  • LAD-120A provides 13.8V main output rated at 7.7A
  • LAD-120B provides 27.6V main output rated at 3.4A
  • LAD-120C provides 41.5V main output rated at 1.9A
  • LAD-120D provides 55.2V main output rated at 1.21A
  • Built-in battery charger and automatic UPS backup operation during abnormal AC input
  • TTL status signals for AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge monitoring
  • Forced UPS mode supports battery maintenance and system testing
  • Short circuit, overload, overvoltage, overtemperature, battery low-voltage and reverse-polarity protection
  • Suitable for lead-acid and lithium-ion batteries
  • Compact 159 × 97 × 30 mm low-profile design with built-in AC and battery circuit ON/OFF switches

Need help selecting the correct output voltage for your system? Compare LAD-120A, LAD-120B, LAD-120C and LAD-120D below.

LAD-120 Series Technical Specifications

The table below compares the main electrical specifications of the MEAN WELL LAD-120 Series, including main DC output, battery charging output, rated power, ripple and noise, voltage adjustment range and typical efficiency.

It helps users compare LAD-120A, LAD-120B, LAD-120C and LAD-120D when selecting a compact 120W security power supply with battery charger and UPS backup function.

Model Main Output Main Output Rated Current Battery Charger Output Charger Rated Current Rated Power Ripple & Noise Max. Voltage Adj. Range Efficiency Typ.
LAD-120A 13.8V 7.7A 13.8V 1A 120W 120mVp-p 10.8–14.5V 86%
LAD-120B 27.6V 3.4A 27.6V 1A 121.4W 150mVp-p 21.6–29V 88%
LAD-120C 41.5V 1.9A 41.5V 1A 120.35W 240mVp-p 32.4–43.5V 88%
LAD-120D 55.2V 1.21A 55.2V 1A 121.99W 360mVp-p 43.5–58V 88%
Common input specifications: 90–264VAC / 127–370VDC, 47–63Hz. Typical AC current is 2.5A at 115VAC and 1.5A at 230VAC. Cold-start inrush current is typically 30A at 115VAC and 55A at 230VAC, while leakage current is 0.5mA at 240VAC.
Output and regulation note: Main output voltage tolerance is ±1.0%, with ±0.5% line regulation and ±0.5% load regulation. CH1 output voltage is adjustable by VR, with an adjustment range of approximately -20% to +5% depending on the model.
Battery and protection note: Battery low-voltage cut-off is 9.5V ±0.5V for LAD-120A, 21.5V ±0.5V for LAD-120B, 32V ±0.5V for LAD-120C and 43V ±0.5V for LAD-120D. The series also provides protection against short circuit, overload, overvoltage, overtemperature and battery reverse polarity.
Status monitoring note: TTL signals are provided for AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge status. An external voltage source is required for the TTL signals, with a maximum applied voltage of 50VDC and maximum sink current of 30mA.
Environment and mechanical note: The LAD-120 Series operates from -20°C to +60°C with output derating at higher ambient temperatures. The low-profile enclosure measures 159 × 97 × 30 mm, making it suitable for compact security, fire alarm, DC UPS and central monitoring installations.

Need more technical details? Continue below for UPS backup operation, TTL status signals, forced UPS mode, battery protection functions, mechanical dimensions, connector assignments, safety approvals, EMC information and application guidance.

Model Selection Guide for LAD-120 Series

The MEAN WELL LAD-120 Series includes four 120W-class AC/DC power supply models with built-in battery charger and UPS backup function. Selection between LAD-120A, LAD-120B, LAD-120C and LAD-120D is primarily determined by the required DC output voltage, load current and battery charging requirements.

All four models share the same 90–264VAC / 127–370VDC input range, 1A battery charging output, UPS backup function, TTL status monitoring, forced UPS mode, battery reverse-polarity protection and compact 159 × 97 × 30 mm low-profile design. The main differences are output voltage, rated current, rated power, voltage adjustment range and battery low-voltage cut-off threshold.

LAD-120A – 13.8V Output

The MEAN WELL LAD-120A provides a 13.8V main output rated at 7.7A together with a 13.8V battery charging output rated at 1A. Rated power is 120W.

The main output voltage can be adjusted from 10.8V to 14.5V. Battery low-voltage cut-off is specified at 9.5V ±0.5V.

LAD-120A is generally selected when the connected load and battery backup architecture require the lowest output-voltage version in the LAD-120 Series.

LAD-120B – 27.6V Output

The MEAN WELL LAD-120B provides a 27.6V main output rated at 3.4A together with a 27.6V battery charging output rated at 1A. Rated power is 121.4W.

The main output voltage can be adjusted from 21.6V to 29V. Battery low-voltage cut-off is specified at 21.5V ±0.5V.

LAD-120B is suitable for systems requiring a 27.6V regulated output with integrated battery charging and UPS backup operation.

LAD-120C – 41.5V Output

The MEAN WELL LAD-120C provides a 41.5V main output rated at 1.9A together with a 41.5V battery charging output rated at 1A. Rated power is 120.35W.

The main output voltage can be adjusted from 32.4V to 43.5V. Battery low-voltage cut-off is specified at 32V ±0.5V.

LAD-120C is intended for higher-voltage backup power architectures requiring a 41.5V regulated output and integrated battery charging.

LAD-120D – 55.2V Output

The MEAN WELL LAD-120D provides a 55.2V main output rated at 1.21A together with a 55.2V battery charging output rated at 1A. Rated power is 121.99W.

The main output voltage can be adjusted from 43.5V to 58V. Battery low-voltage cut-off is specified at 43V ±0.5V.

LAD-120D is the highest-voltage model in the series and is suitable where the connected load and backup battery architecture require a 55.2V output.

How to Choose Between LAD-120A, LAD-120B, LAD-120C and LAD-120D

Start with the required DC output voltage. Choose LAD-120A for 13.8V, LAD-120B for 27.6V, LAD-120C for 41.5V or LAD-120D for 55.2V output.

Then confirm the required load current. LAD-120A provides up to 7.7A, LAD-120B up to 3.4A, LAD-120C up to 1.9A and LAD-120D up to 1.21A. All four models provide a dedicated 1A battery charging output.

When AC input is normal, the LAD-120 supplies the connected load while charging the external battery. When the AC input becomes abnormal, the built-in UPS function switches the system to battery backup operation.

Status Monitoring and UPS Control

All LAD-120 models provide TTL status signals for AC OK, battery disconnect or reverse polarity, battery low, battery full and discharge status. The TTL interface requires an external voltage source and supports up to 50VDC applied voltage with a maximum sink current of 30mA.

The series also provides a forced UPS mode through CN2 pins 7 and 8. Shorting these pins activates forced UPS operation, while leaving them open keeps the unit in normal operating mode.

Need help choosing the correct LAD-120 model? Start with the required output voltage, then confirm load current, battery charging requirements, backup operation and monitoring interface requirements.

Related MEAN WELL LAD, PSC and Security Power Supplies

For security systems, fire alarm systems, emergency power, central monitoring and battery backup applications, the following MEAN WELL power supplies can be compared with the LAD-120 Series according to required output power, output voltage, battery charging capability, UPS function, monitoring requirements and installation format:

  • LAD-240 Series – Higher-power LAD Series security and fire alarm power supply with integrated battery charger, UPS backup function and system monitoring for applications requiring more output capacity than LAD-120.
  • LAD-360 Series – Higher-capacity LAD Series power supply for security, fire alarm and battery backup systems requiring greater load power and charging capability.
  • LAD-600 Series – High-power LAD Series security and emergency backup power solution for systems requiring substantially greater output capacity, battery charging and UPS operation.
  • PSC-35 Series – Lower-power AC/DC power supply with integrated battery charger and UPS backup function for security and battery-backed DC applications with lighter load requirements.
  • PSC-60 Series – Compact 60W power supply with battery charger and UPS function for applications requiring lower output power than LAD-120.
  • PSC-100 Series – 100W battery charger power supply with UPS backup function for security, alarm and DC backup applications requiring lower output power.
  • PSC-160 Series – Higher-power 160W AC/DC power supply with integrated battery charger and UPS backup function for systems requiring greater load and charging capacity.
  • DRC-60 Series – DIN rail AC/DC power supply with integrated battery charger and UPS function for systems that require TS35 rail installation.
  • DRC-100 Series – DIN rail security power supply with battery charging and automatic backup operation for higher-power DIN rail applications.
  • DRS-240 Series – Intelligent DIN rail security power supply integrating AC/DC power, battery charger, DC UPS, status monitoring and communication functions for advanced backup power systems.

Need help selecting the right MEAN WELL security power supply?
Compare LAD, PSC, DRC and DRS Series based on required output voltage, load power, battery charging current, UPS backup operation, status monitoring, communication functions and installation format.

Battery Backup and Status Monitoring Functions

The MEAN WELL LAD-120 Series integrates battery charging, UPS backup control and multiple TTL status signals for security, fire alarm and DC backup systems that require continued operation and external status monitoring during AC mains interruption.

Battery Backup Operation

During normal AC operation, the LAD-120 supplies power to the connected load while charging the external battery. If the AC input becomes abnormal, the built-in UPS function switches the power source to battery backup so the connected load can continue operating.

The series includes four output versions: LAD-120A at 13.8V, LAD-120B at 27.6V, LAD-120C at 41.5V and LAD-120D at 55.2V. Each model also provides a dedicated 1A battery charging output.

Battery protection note: An external fuse is mandatory in series with the battery connection for protection.

TTL Status Monitoring

The LAD-120 Series provides multiple TTL status signals through the CN2 interface for external monitoring and control:

  • AC OK: Indicates whether the AC input is normal or abnormal
  • Battery Disconnect / Reverse Polarity: Detects battery connection status or reverse-polarity condition during initial power transmission
  • Battery Low: Indicates a low-battery condition
  • Battery Full: Indicates whether the battery is still charging or has reached full-charge status
  • Discharge: Indicates whether the system is operating from battery backup

The TTL interface requires an external voltage source and supports a maximum applied voltage of 50VDC with a maximum sink current of 30mA.

Battery detection note: The battery disconnect and reverse-polarity signals can only be detected during the initial power transmission and are not continuously available for real-time detection at all times.

Battery Low-Voltage Cut-Off Protection

To help prevent excessive battery discharge during extended backup operation, the LAD-120 Series includes battery low-voltage cut-off protection:

  • LAD-120A: 9.5V ±0.5V battery cut-off
  • LAD-120B: 21.5V ±0.5V battery cut-off
  • LAD-120C: 32V ±0.5V battery cut-off
  • LAD-120D: 43V ±0.5V battery cut-off

The series also provides battery reverse-polarity protection. If the battery is connected with reversed polarity, the unit is protected from damage and recovers automatically after the fault condition is removed.

Forced UPS Mode

For battery maintenance and system testing, the LAD-120 Series provides a forced UPS mode through CN2 pins 7 and 8.

When pins 7 and 8 are shorted, the unit enters forced UPS mode. When the pins are open, the unit operates normally. This function allows the battery backup path to be tested without waiting for an actual AC mains failure.

Need wiring and connector details? Continue below to review the LAD-120 mechanical drawing, CN2 TTL signal pin assignment, terminal assignment and installation information.

MEAN WELL LAD-120 Series mechanical drawing and dimensions
MEAN WELL LAD-120 Series mechanical drawing showing overall dimensions, mounting details, terminal assignments and CN2 connector layout.

Mechanical Dimensions and Installation

The MEAN WELL LAD-120 Series uses a compact low-profile mechanical design intended for integration into security, fire alarm, battery backup and DC UPS equipment. The series has a height of only 30 mm, helping reduce enclosure space requirements in compact system designs.

Dimensions

The LAD-120 Series measures 159 × 97 × 30 mm (L × W × H) and uses Case No. 241.

The mechanical drawing identifies the mounting-hole positions, terminal block, CN2 signal connector, AC ON/OFF switch, battery connected/disconnected switch and airflow direction. The same mechanical platform is used across the LAD-120 Series.

TB1 Terminal Assignment

The main power and battery connections are provided through the TB1 terminal block:

  • Pin 1: AC/L
  • Pin 2: AC/N
  • Pin 3: FG
  • Pin 4: DC OUTPUT -V
  • Pin 5: DC OUTPUT +V
  • Pin 6: BAT –
  • Pin 7: BAT +
Important wiring note: DC OUTPUT -V and BAT – must not be shorted together.

CN2 TTL Signal Assignment

The CN2 connector provides status monitoring and forced UPS control signals:

  • Pin 1: AC OK
  • Pin 2: Battery disconnect / reverse polarity
  • Pin 3: Battery Low
  • Pin 4: GND
  • Pin 5: Battery Full
  • Pin 6: Discharge
  • Pins 7 and 8: Open for normal operation; short for forced UPS mode

The specified CN2 mating components are TKP DH2 or equivalent for the housing and TKP DHT-1S(LF) or equivalent for the terminal.

Operating Environment and Derating

The LAD-120 Series is specified for operation from -20°C to +60°C. Output load should be reduced as ambient temperature increases beyond the full-load operating region.

The mechanical design also defines the required airflow direction. Adequate ventilation should be provided when the power supply is installed inside the final equipment enclosure.

Mechanical Drawing and Installation Reference

The LAD-120 mechanical drawing shows overall dimensions, mounting points, TB1 terminal locations, CN2 connector position, AC ON/OFF switch, battery connected/disconnected switch and airflow direction.

For final enclosure design and wiring, review the official LAD-120 Series datasheet and MEAN WELL installation manual to confirm mounting dimensions, connector details, wiring requirements and installation conditions.

Need complete installation details? Use the mechanical drawing above together with the installation documentation to verify mounting, TB1 wiring, CN2 TTL signal connections and forced UPS control.

Applications

The MEAN WELL LAD-120 Series is designed for security, fire alarm and backup power applications requiring regulated DC output, battery charging, UPS operation and external status monitoring.

With LAD-120A, LAD-120B, LAD-120C and LAD-120D covering 13.8V, 27.6V, 41.5V and 55.2V output versions, the series provides a flexible platform for systems that require continuous DC operation, battery-supported backup and TTL status detection.

  • Fire emergency and evacuation systems requiring reliable DC power, battery charging and backup operation during abnormal AC input
  • Security systems requiring regulated DC power together with battery backup and system status monitoring
  • Public safety battery backup systems requiring continued operation from an external battery during AC mains interruption
  • Uninterruptible DC-UPS systems requiring automatic transfer to battery-supported operation when AC input becomes abnormal
  • Central monitoring systems using TTL signals for AC OK, battery status, battery low, battery full and discharge monitoring
  • Industrial automation systems requiring regulated DC output, battery charging and backup power integration

Need safety and compliance details for your project? Continue below to review protection functions, safety approvals, EMC compliance and operating environment specifications for the LAD-120 Series.

Certifications and Safety

The MEAN WELL LAD-120 Series is designed as a 120W AC/DC security and fire alarm power supply with integrated battery charging, UPS backup and status monitoring functions for systems requiring continued DC operation during abnormal AC input conditions.

The series is approved to UL62368-1, BS EN/EN62368-1, AS/NZS62368.1 and EAC TP TC 004. Its design also refers to GB 17945-2010 system requirements.

Safety and EMC Compliance

The LAD-120 Series is specified with the following safety and EMC standards:

  • UL62368-1 safety approval
  • BS EN/EN62368-1 safety approval
  • AS/NZS62368.1 safety approval
  • EAC TP TC 004 safety approval
  • GB 17945-2010 referenced in the product design requirements
  • BS EN/EN55032 (CISPR32) Class A conducted and radiated EMC emissions
  • BS EN/EN61000-3-2 Class A harmonic current requirements
  • BS EN/EN61000-4-2, -4-3, -4-4, -4-5, -4-6 and -4-8 EMC immunity tests
  • EAC TP TC 020 EMC requirements

Isolation and Electrical Safety

Withstand voltage ratings are:

  • Input to output: 3KVAC
  • Input to FG: 2KVAC
  • Output to FG: 0.5KVAC

Isolation resistance is specified at 100MΩ between input-output, input-FG and output-FG when tested at 500VDC, 25°C and 70% RH.

Protection Functions

The LAD-120 Series includes protection against short circuit, overload, overvoltage, overtemperature, battery low voltage and battery reverse polarity.

Overload behavior depends on the operating condition. With a battery connected, the unit can enter UPS operation under CH1 overload conditions, while excessive combined CH1 and CH2 loading can cause hiccup protection. Without a battery connected, overload protection follows the applicable model and operating condition.

Overvoltage and overtemperature protection shut down the output and require the power supply to be re-powered after the fault condition is removed. Battery reverse-polarity protection prevents damage and automatically recovers after correct battery connection is restored.

Operating Environment and Final Equipment Integration

The LAD-120 Series operates from -20°C to +60°C, with output derating at higher ambient temperatures.

The power supply is intended for integration into final equipment. EMC performance is therefore also influenced by the completed system, including enclosure design, grounding, wiring and installation conditions.

System designers should verify wiring, grounding, enclosure layout, thermal conditions, airflow and EMC performance in the final installation.

Need more product details before sending an inquiry? Continue below to review model comparison, battery backup operation, TTL status signals, forced UPS mode, mechanical dimensions, installation guidance and application information for the LAD-120 Series.

FAQ

What is the MEAN WELL LAD-120 Series?

The MEAN WELL LAD-120 Series is a 120W-class AC/DC security and fire alarm power supply with a built-in battery charger and UPS backup function. It is designed for applications that require regulated DC output, battery charging and continued operation from an external battery when the AC input becomes abnormal.
The series includes LAD-120A, LAD-120B, LAD-120C and LAD-120D, covering 13.8V, 27.6V, 41.5V and 55.2V output versions.

What is the difference between LAD-120A, LAD-120B, LAD-120C and LAD-120D?

The main difference is the DC output voltage and rated load current:
– LAD-120A: 13.8V, 7.7A
– LAD-120B: 27.6V, 3.4A
– LAD-120C: 41.5V, 1.9A
– LAD-120D: 55.2V, 1.21A
All four models provide a dedicated 1A battery charging output. Selection should therefore begin with the required system voltage and then confirm the load-current requirement.

Does the MEAN WELL LAD-120 have a built-in battery charger?

Yes. The LAD-120 Series has a built-in battery charger and provides a separate 1A charging output for the external backup battery.
During normal AC operation, the power supply can operate the connected DC load while charging the battery. If the AC supply becomes abnormal, the UPS function allows the battery to support the connected load.

How does the LAD-120 UPS function work?

When AC input is normal, the LAD-120 supplies the DC load and charges the connected battery. When the AC input becomes abnormal, the built-in UPS function switches the system to battery-supported operation.
When the AC mains returns to normal, the load is again supplied from the AC source and the battery can resume charging. This makes the LAD-120 suitable for security, fire alarm and other systems that need DC backup during a mains interruption.

Can the LAD-120 be used with lithium-ion batteries?

Yes. MEAN WELL specifies that the LAD-120 Series is suitable for both lead-acid and lithium-ion batteries.
However, the battery voltage, charging characteristics, protection requirements and any required battery management system should be verified for the specific battery pack before installation.

What status signals are available on the LAD-120 Series?

The LAD-120 provides TTL status signals for:
– AC OK
– Battery disconnect / reverse polarity
– Battery low
– Battery full
– Discharge

These signals are available through the CN2 interface and can be connected to external monitoring or control equipment. The interface supports a maximum external applied voltage of 50VDC and a maximum sink current of 30mA.

What is the forced UPS mode on the LAD-120?

The forced UPS mode allows the LAD-120 to enter battery-supported operation for maintenance or testing without waiting for an actual AC mains failure.

Shorting CN2 pins 7 and 8 activates forced UPS mode, while leaving the pins open keeps the unit in normal operation. This function is useful for checking the backup battery and UPS path during maintenance.

What are the battery low-voltage cut-off levels for LAD-120?

The battery low-voltage cut-off thresholds depend on the model:
– LAD-120A: 9.5V ±0.5V
– LAD-120B: 21.5V ±0.5V
– LAD-120C: 32V ±0.5V
– LAD-120D: 43V ±0.5V
This protection helps prevent excessive battery discharge during prolonged backup operation.

What are the dimensions of the MEAN WELL LAD-120 Series?

The LAD-120 Series measures 159 × 97 × 30 mm.
Its 30 mm height provides a 1U low-profile design, making it suitable for compact security, fire alarm, monitoring and DC UPS enclosures where installation height is limited.

What applications is the LAD-120 Series designed for?

MEAN WELL lists the LAD-120 Series for applications including:
– fire emergency and evacuation systems
– public safety battery backup
– security systems
– uninterruptible DC-UPS systems
– central monitoring systems
– industrial automation
Its combination of battery charging, UPS backup and TTL status monitoring makes it particularly suitable for systems that need both backup power and external operating-status supervision.

Need more details about LAD-120A, LAD-120B, LAD-120C or LAD-120D output voltage, battery charging current, UPS backup operation, TTL status signals, battery low-voltage cut-off, forced UPS mode, protection functions and installation? Check the FAQs above or review the official LAD-120 Series datasheet for complete electrical, battery backup, mechanical and installation specifications.

Product Video

MEAN WELL LAD-120 Series Power Supply Unboxing

MEAN WELL LAD-120 Series Power Supply Video Show

LAD-120 Series product videos will be added soon.

Request a Quote

Need pricing, stock availability, lead time, or project support for the MEAN WELL LAD-120 Series? Continue below to send your inquiry for LAD-120A, LAD-120B, LAD-120C or LAD-120D, including your required quantity, output voltage, load current, battery charging requirements, backup operation, TTL status monitoring requirements, and application details.

LAD-120 Series
This website uses cookies to improve your experience. By using this website you agree to our Data Protection Policy.
Read more